Name: A Biao
Tel: 0577-61568760
Phone:13506559954
WeChat:86+13506559954
Whatsapp:86+15381506128
Instagram:qichuangp
YouTube:qicuang@gmail.com
facebook:https://www.facebook.com/profile.php?id=100087300828460
twitter:@QichuangP
trademanager:qichuangpower
E-mail:qicuang@gmail.com
Add:2188 Liuhuang Road, Liushi Town, Yueqing City, Wenzhou City, Zhejiang Province
Whatsapp WeChat
Product Overview
The XMG-1 series reclosing controller is specially designed for the intelligent control of the switch body, with quick-break, overcurrent three-stage, zero-sequence protection and reclosing functions. The controller is electrically connected to the switch body through the control cable and aerial connectors to achieve its protection and automatic monitoring functions. The product is widely used in urban and rural 35kV transmission line users.
Technical specifications
Main application and scope of application
The XMG-1 series reclosing controller is specially designed for the intelligent control of the switch body, with quick-break, three-stage overcurrent, zero-sequence protection and reclosing functions. The controller is electrically connected to the switch body through control cables and airline connectors to achieve its protection and automatic monitoring functions. The product is widely used in urban and rural 35kV transmission line users.
Environmental conditions of use
a) Altitude: s2000m
b) Ambient temperature: -40°C- +80°C Maximum annual average temperature 20°C. Maximum average daily temperature 30°C
c) Seismic capacity: horizontal ground acceleration 0.3g. vertical acceleration 0.15g. simultaneous action of three sine waves with a safety factor of 1.67
d) Maximum daily temperature difference: 25℃
e) Neutral grounding mode: neutral point is not grounded, neutral point is grounded by arc extinguishing coil, neutral point is grounded by low resistance
Product quality responsibility
Before the controller is put into operation, please read this manual in detail, for violation of the operation of the equipment damage caused by my company is not responsible.
Serial number | Name | Unit | Data | Remarks |
1 | Rated voltage | kV | ||
2 | Rated current | A | ||
3 | Rated short-circuit closing current (peak) | kA | ||
4 | Rated current switching performance | times | ||
5 | Breaking time | ms | ||
6 | Closing bounce time | ms | ||
7 | Switch closing (breaking) simultaneity | ms | ||
8 | Built-in line current transformer variation | :5 | ||
9 | Breaking and closing voltage | V | 220V | DC |
Serial number | Projects | Prescribed values | Remarks |
1 | Input operating voltage | AC220V | +/-20% |
2 | Input operating voltage frequency | 50Hz | |
3 | Permissible fluctuation range of the input operating voltage | ±20% | |
4 | Power consumption of the whole machine | <10W | |
5 | Output voltage (breaking and closing operation) | Depending on the switch option | |
6 | Output control contact capacity | Adjustable | |
7 | Sampling phase current input value | 0~100A | Secondary current above 100A allowed to saturate |
8 | Sampling zero sequence current input value | 0~5A | Zero sequence secondary current allowed to saturate above 5A |
9 | Allowable sampling error of power input value | ±3% | Saturation zone is not required |
10 | Same protection current adjustment value range | 1A~100A | Secondary currents |
11 | Same protection action delay time value | 20ms~10s | Adjustable |
12 | Range of zero sequence protection current setting values | 0-5A | Secondary currents |
13 | Zero sequence protection action delay time value | 0~60000S | Adjustable |
14 | Number of reclosures | 3 times adjustable | |
15 | First reclosing time | Adjustable | 5~600.0S |
16 | Second reclosing time | Adjustable | 5~600.0S |
17 | Third reclosing time | Adjustable | 5~600.0S |
18 | Adjustment error | ±3% | |
19 | Insulation impedance | >100MΩ/DC500V | 1. External terminals together to ground 2. Power input to power, switch control output terminals 3.Switching status input terminal to power supply, switch control output terminal |
20 | Frequency withstand voltage | 2000V/1min | Ibid |
21 | Shock withstand voltage | 5000V,1.2/50us three times positive and negative | 1. Power supply and switch control output terminals together to ground 2. Power input terminals together to ground |
Functions and features
Functions of the controller
◇Quick-break protection ◇Overcurrent protection ◇Three times reclosing ◇Event memory view ◇Surge protection ◇Three-stage protection
Zero-sequence protection ◇Real-time clock ◇Post-acceleration ◇Real-time status enquiry ◇Inverse time limit
Features of the controller
◇Acceleration function after reclosing: When the switch is reclosed in permanent fault, it will accelerate tripping: ◇
◇Remote-controlled closing accelerates tripping and latches reclosing: if the user sends power after overhauling the line, it should accelerate tripping if it forgets to remove the grounding knife gate.
◇The delay time for all three reclosures can be adjusted.
◇The tripping circuit is designed to prevent misoperation and has an anti-trip function.
◇The zero sequence current can distinguish between in-zone and out-of-zone faults; only the remote-controlled breaking and closing circuit is designed to prevent misoperation.
◇The three-stage protection function can independently realize four sets of anti-time-limit curves.
◇The three-stage post-acceleration function can be independently activated or closed.
Structural features
a) The controller is a microcomputer type seam power protection and monitoring device.
b) The controller has the protective features of strong weather resistance and condensation resistance.
c) Connection to the switch body is made through an airline connector.
d 1 Good connection reliability and high protection level.
The controller has 5 analog input channels, A-phase current, B-phase current, C-phase current, zero-sequence current, and C-phase current. Zero sequence current. Single-side voltage. The controller monitors the above analogue values in real time and compares them with the fixed values to determine line faults, so that they can be processed accordingly.
0577-61568760
86+15381506128
86+13506559954