Name: A Biao
Tel: 0577-61568760
Phone:13506559954
WeChat:86+13506559954
Whatsapp:86+15381506128
Instagram:qichuangp
YouTube:qicuang@gmail.com
facebook:https://www.facebook.com/profile.php?id=100087300828460
twitter:@QichuangP
trademanager:qichuangpower
E-mail:qicuang@gmail.com
Add:2188 Liuhuang Road, Liushi Town, Yueqing City, Wenzhou City, Zhejiang Province
Whatsapp WeChat
Model :
Number :
Weight :
Product overview
Automatic reclosing type intelligent three-phase residual current action circuit breaker integrates the main functions of traditional circuit breaker (fuse), contactor, overload (or over-voltage, leakage, etc.) protection relay, starter, isolator, etc., with remote automatic control and local direct control function, panel display and signal alarm function, with over-voltage protection, under-voltage protection, over-current protection, leakage protection, etc., with Small size, high reliability, strong short-circuit breaking capacity, short flying arc distance and other advantages. It is suitable for low-voltage grids of three-phase four-wire neutral point direct grounding TT grounding systems. It is used to provide indirect contact protection against the risk of personal electric shock and also to protect against earth faults, over-currents and short-circuits in the line or in the use of electricity.
Technical parameters
Automatic reclosing type intelligent three-phase residual current action circuit breaker integrates the main functions of traditional circuit breaker (fuse), contactor, overload (or over-voltage, leakage, etc.) protection relay, starter, isolator, etc., with remote automatic control and local direct control function, panel display and signal alarm function, with over-voltage protection, under-voltage protection, over-current protection, leakage protection, etc., with Small size, high reliability, strong short-circuit breaking capacity, short flying arc distance and other advantages. It is suitable for low-voltage grids of three-phase four-wire neutral point direct grounding TT grounding systems. It is used to provide indirect contact protection against the risk of personal electric shock and also to protect against earth faults, over-currents and short-circuits in the line or in the use of electricity.
Product features
◇Power parameter measurement function: real-time measurement of voltage, current and leakage current data of power supply lines.
◇Multi-functional protection function: with various protection such as leakage, over-voltage, under-voltage, over-current and short-circuit.
◇Remote monitoring function: With RS485 communication interface, it can realize remote control and intelligent centralized management.
◇Fault enquiry function: Manual inquiry/software enquiry for the last 10 fault phenomena.
◇Event recording function: Record the accumulated number of faults; the last 10 fault phenomena and fault values.
◇Automatic reclosing: it can automatically reclose after restoration of leakage, overvoltage and undervoltage faults.
External and mounting dimensions in mm
| Specification | Dimensions | Mounting dimensions | |||||
| A | B | E | H | G | C | D | |
| 100A | 230 | 121 | 48 | 62 | 170 | 60 | 210 |
| 225A | 240 | 142 | 48 | 83 | 179 | 70 | 202 |
| 400A | 336.5 | 197.5 | 87 | 99 | 274 | 95 | 274 |
| 630A 800A | 355 | 240 | 88 | 111 | 269 | 116 | 285 |
Technical parameters
Rated working voltage Un: AC 3x220/380V 50Hz
Rated operating current le: Can be set within the permissible range shown in the table below.
| Frame rated current In | Effective measuring range | Rated action current le | Factory settings |
| 100A | 2.5-500A | 20A-100A with a step difference of 1A | 100A |
| 225A | 4.5-1125A | 45A-225A with 1A step difference | 225A |
| 400A | 8.0-2000A | 80A-400A with 1A step difference | 400A |
| 800A | 16.0-3200A | 160A-800A with 1A step difference | 800A |
Automatic reclosing time: 20~60 seconds
● Leakage protection function
Rated residual action current setting value lΔn: 50~990mA can be set, 10mA step difference, factory default is 500mA
Rated residual non-action current lΔno:=0.8lΔn
Rated residual action current maximum breaking time: <0.5sec
Leakage fault action mode: optional
Breakage/phase failure can be selected by the user: optional
Automatic reclosing after recovery from leakage fault.
● Overcurrent protection function
Overcurrent inverse time delay protection curve code: 1~6, factory default is 1
Overcurrent fault action mode: optional
Overcurrent fault does not automatically reclose.
Overcurrent inverse time limit fault delay action schedule.

Note: lw in the table is the operating current and ln is the rated action current.
Overcurrent inverse time delay protection curve diagram

● Short-circuit protection function:
Short-circuit fault mechanical thermal protection
No automatic reclosing for short-circuit faults.
● Break/phase loss, under-voltage, over-voltage protection:
Undervoltage protection value: 176V by factory default
Overvoltage protection value: 264V by factory default
Voltage fault action mode: optional
Voltage fault can be selected by the user: optional
Voltage fault can be automatically reclosed after recovery.
0577-61568760
86+15381506128
86+13506559954